Everything in the generator room that isn't the set itself: battery charger, fuel transfer, jacket heater, room ventilation and lighting.

Rating plate
DG Aux Panel
Most standby sets that fail to start fail on the battery. The charger and its healthy/fail alarm belong on the auxiliary panel, monitored, not on a plug top behind the set.
Interlock the louvres with the set. A generator started into a closed ventilation louvre pulls its own exhaust back through the radiator and trips on high water temperature within minutes.