Mushroom-head emergency stop — latching, twist to release, on a hardwired circuit that does not pass through the PLC.

Rating plate
Emergency Push Button Station
The contacts are direct-opening: a welded contact is forced apart mechanically by the actuator, so the circuit breaks even when the contact block has failed. A standard NC contact does not do this.
Never route an emergency stop through the PLC. It goes to a safety relay or a safety-rated input, so a processor fault or a scan halt cannot leave the stop unanswered.
Stop category 0 removes power immediately; category 1 brings the drive to a controlled stop first, then removes power. Category 1 is the right choice where an immediate stop is itself dangerous — a spinning saw, a loaded hoist.
The assembly is ours; the switchgear inside it is genuine, authorised-channel product from the makes you specify.
Built to the same standard, and able to share a lineup with this one.

Marshalling · IP65

Start/stop · Lockable

PCC · 6300 A · Form 3b/4

MCC · 4000 A · Draw-out
A drawing, a load list or a BOQ is enough to start. You'll get the ratings checked against the actual fault level, a general-arrangement drawing to approve, and a fixed price.