The board on the UPS output, with the maintenance bypass that lets the UPS be taken out without dropping the load it protects.

Rating plate
UPS Main Distribution Board
Make-before-break is the whole point of the bypass. A break-before-make switch drops the load for the transfer, which is exactly the event the UPS was bought to prevent.
Size the neutral at 200%. UPS output feeds switch-mode supplies almost exclusively, and their third-harmonic currents sum in the neutral rather than cancelling.
The assembly is ours; the switchgear inside it is genuine, authorised-channel product from the makes you specify.
Built to the same standard, and able to share a lineup with this one.

MDB · 2000 A · Floor standing

SDB · 400 A · Wall or floor

USDB · Final · Per-rack
A drawing, a load list or a BOQ is enough to start. You'll get the ratings checked against the actual fault level, a general-arrangement drawing to approve, and a fixed price.